6ES7416-2XN05-0AB0,西門子6ES74162XN050AB0,西門子S7-400CPU416-2DP,西門子CPU416-2DP,CPU416-2DP,SIMATIC S7-400,CPU 416-2DP: 5.6MB(2.8MB代碼,2.8MB數(shù)據(jù)),位處理速度30ns,集成接口:1. MPI/DP, 2. PROFIBUS DP
6ES7416-2XN05-0AB0 SIMATIC S7-400,CPU 416-2DP: 5.6MB(2.8MB代碼,2.8MB數(shù)據(jù)),位處理速度30ns,集成接口:1. MPI/DP, 2. PROFIBUS DP |
德國* 現(xiàn)貨銷售 質(zhì)保一年 歡迎詢價(jià)
SIEMENS 上海翰粵自動(dòng)化系統(tǒng)有限公司
瞿曉明(銷售工程師) | |
手 機(jī) | |
1324375156 | |
電 話 |
概述
- 性能范圍內(nèi)的高性能 CPU
- 適用于對性能要求很高的工廠
- CPU 416-3 PN/DP 中集成了 PROFINET 功能
CPU 416-2, CPU 416-3 and CPU 416-3 PN/DP are powerful SIMATIC S7-400 CPUs.
The integrated PROFIBUS DP interfaces in the CPU 416-2 and CPU 416-3 make it possible to connect directly to the PROFIBUS DP fieldbus as a master or slave.
An additional DP master system can be connected to the CPU 416-3 and CPU 416-3 PN/DP using the IF 964-DP interface module.
The integrated PROFINET interface of the CPU 416-3 PN/DP includes switch functionality when the ERTEC 400-ASIC is used. This forms the basis for providing two externally accessible PROFINET ports. In addition to hierarchical network topologies, this also enables the creation of line structures in the new S7-400 controllers.
Note:
Only the 6ES7 964-2AA04-0AB0 interface submodule may be used.
設(shè)計(jì)
Both CPUs are equipped with the following:
- Powerful processor:
The CPUs achieve instruction execution times as low as 0.03 µs per binary instruction. - CPU 416-2: 5.6 MB RAM (of which 2.8 MB each for program and data);
CPU 416-3: 11.2 MB RAM (of which 5.6 MB each for program and data);
CPU 416-3 PN/DP: 11.2 MB RAM (of which 5.6 MB each for program and data);
fast RAM for parts of the user program relevant to execution. - Flexible expansion:
Up to 262144 digital and 16384 analog inputs/outputs. - Multi-point interface MPI:
With the MPI it is possible to establish simple networking of max. 32 stations at a data transmission rate of up to 12 Mbit/s. The CPUs can establish up to 44 connections to stations of the communications bus (C bus) and the MPI. - Mode selector switch:
Designed as toggle switch. - Diagnostics buffer:
The last 120 fault and interrupt events are retained in a ring buffer for diagnostic purposes. The number of entries can be parameterized. - Real-time clock:
The date and time are appended to diagnostic messages of the CPU. - Memory card:
For expansion of the integrated load memory. RAM and FEPROM cards (FEPROM for retentive storage) are available - Combined MPI/DP interface and integrated PROFIBUS DP interface (CPU 416-2 and CPU 416-3):
The PROFIBUS DP master interface allows a distributed automation configuration offering high speed and ease of use. From the user's point of view, the distributed I/O is treated as central I/O (same configuring, addressing and programming).
Mixed configuration: SIMATIC S5 and SIMATIC S7 as PROFIBUS master according to EN 50170.
CPU 416-3 and CPU 416-3 PN/DP also include:
- A module slot:
An additional PROFIBUS DP master system can be connected via the IF 964-DP interface module.
CPU 416-3 PN/DP additionally includes:
- PROFINET interface with 2 ports (switch):
- PROFINET I/O, 256 IO devices connectable
- PROFINET CBA
功能
- Block protection:
A password concept protects the user program from unauthorized access. - Integral HMI services:
The user only has to specify the source and destination of the data with HMI devices. The data are then transported cyclically and automatically by the system. - Integrated communications functions:
- PG/OP communication
- Shared data communication
- S7 standard communication
- S7 communication
- Firmware update using network
CPU 416-3 PN/DP additional:
- Open communication over TCP/IP, UDP and ISO-on-TCP (RFC1006)
- Distributed inligence in Component Based Automation (CBA) on PROFINET
- Additional diagnostic options with integrated web server
Parameterizable attributes
The STEP 7 tool "Hardware Configuration" can be used to program the properties and response of the S7-400 including the CPUs, e.g.
- Multi-point interface MPI:
- Definition of station addresses.
- Startup/cycle behavior
- Stipulation of the maximum cycle time and communications load
- Address assignment:
Addressing of I/O modules. - Retentive ranges:
Definition of the number of retentive bit memories, counters, timers, data blocks and clock memories. - Size of the process image, local data.
- Length of the diagnostics buffer
- Protection level:
Definition of access authorization for program and data - System diagnostics:
Definition of the handling and scope of diagnostic messages - Timed interrupts:
Setting of periodicity
CPU 416-3 PN/DP additional:
- PROFINET interface
- Parameterization of time synchronization using NTP procedure
Indication and information functions
- Status and error indicators:
LEDs indicate internal and external errors and operating states such as RUN, STOP, Restart, Test function, for example - Test functions:
The programming device can be used to display signal states in program execution, modify process tags irrespective of the user program, read out the contents of stack memories, run separate program steps and inhibit program components - Information functions:
The programming device can be used to provide the user with information on the memory capacity and operating mode of the CPU and the current utilization of the working and load memories
Order number | 6ES7416-2XP07-0AB0 | 6ES7416-3XS07-0AB0 | 6ES7416-3ES07-0AB0 | |
---|---|---|---|---|
| CPU 416-2, MPI, PROFIBUS, 8 MB | CPU 416-3, 16 MB, 3 INTERFACES | CPU416-3 PN/DP, 16 MB, 3 INTERFACES | |
General information |
|
|
| |
Product type designation | CPU 416-2 | CPU 416-3 | CPU416-3 PN/DP | |
Engineering with |
|
|
| |
| STEP 7 V5.4 or higher with HSP 261 | STEP 7 V5.4 or higher with HSP 261 | STEP 7 V5.5 or higher with HSP 262 | |
Supply voltage |
|
|
| |
Rated value (DC) |
|
|
| |
| No; Power supply via system power supply | No; Power supply via system power supply | No; Power supply via system power supply | |
Power loss |
|
|
| |
Power loss, typ. | 4.5 W | 5.5 W | 6.5 W | |
Memory |
|
|
| |
Work memory |
|
|
| |
| 8 Mbyte | 16 Mbyte | 16 Mbyte | |
| 4 Mbyte | 8 Mbyte | 8 Mbyte | |
| 4 Mbyte | 8 Mbyte | 8 Mbyte | |
Load memory |
|
|
| |
| 64 Mbyte | 64 Mbyte | 64 Mbyte | |
| 1 Mbyte | 1 Mbyte | 1 Mbyte | |
| 64 Mbyte | 64 Mbyte | 64 Mbyte | |
CPU processing times |
|
|
| |
for bit operations, typ. | 12.5 ns | 12.5 ns | 12.5 ns | |
for word operations, typ. | 12.5 ns | 12.5 ns | 12.5 ns | |
for fixed point arithmetic, typ. | 12.5 ns | 12.5 ns | 12.5 ns | |
for floating point arithmetic, typ. | 25 ns | 25 ns | 25 ns | |
Counters, timers and their retentivity |
|
|
| |
S7 counter |
|
|
| |
| 2 048 | 2 048 | 2 048 | |
IEC counter |
|
|
| |
| Yes | Yes | Yes | |
S7 times |
|
|
| |
| 2 048 | 2 048 | 2 048 | |
IEC timer |
|
|
| |
| Yes | Yes | Yes | |
Data areas and their retentivity |
|
|
| |
Flag |
|
|
| |
| 16 kbyte; Size of bit memory address area | 16 kbyte; Size of bit memory address area | 16 kbyte; Size of bit memory address area | |
Address area |
|
|
| |
I/O address area |
|
|
| |
| 16 kbyte | 16 kbyte | 16 kbyte | |
| 16 kbyte | 16 kbyte | 16 kbyte | |
Process image |
|
|
| |
| 16 kbyte | 16 kbyte | 16 kbyte | |
| 16 kbyte | 16 kbyte | 16 kbyte | |
Time of day |
|
|
| |
Clock |
|
|
| |
| Yes | Yes | Yes | |
Operating hours counter |
|
|
| |
| 16 | 16 | 16 | |
Interfaces |
|
|
| |
Interfaces/bus type | 1 x MPI/PROFIBUS DP, 1 x PROFIBUS DP | 1 x MPI/PROFIBUS DP, 1 x PROFIBUS DP, 1 x PROFIBUS DP (optionally pluggable) | 1 x MPI/PROFIBUS DP, 1 x PROFINET (2 ports), 1 x PROFIBUS DP (optionally pluggable) | |
Number of RS 485 interfaces | 2; Combined MPI / PROFIBUS DP and PROFIBUS DP | 2; Combined MPI / PROFIBUS DP and PROFIBUS DP | 1; Combined MPI / PROFIBUS DP | |
Number of other interfaces |
| 1; PROFIBUS DP with IF 964-DP (plug-in option; MLFB: 6ES7964-2AA04-0AB0) | 1; PROFIBUS DP with IF 964-DP (plug-in option; MLFB: 6ES7964-2AA04-0AB0) | |
1. Interface |
|
|
| |
Interface type | Integrated | Integrated | Integrated | |
Physics | RS 485 / PROFIBUS + MPI | RS 485 / PROFIBUS + MPI | RS 485 / PROFIBUS + MPI | |
Functionality |
|
|
| |
| Yes | Yes | Yes | |
| Yes | Yes | Yes | |
| Yes | Yes | Yes | |
DP master |
|
|
| |
| 32 | 32 | 32 | |
2. Interface |
|
|
| |
Interface type | Integrated | Integrated | PROFINET | |
Physics | RS 485 / PROFIBUS | RS 485 / PROFIBUS | Ethernet RJ45 | |
Interface types |
|
|
| |
|
|
| 2 | |
Functionality |
|
|
| |
| Yes | Yes | No | |
| Yes | Yes | No | |
|
|
| Yes | |
|
|
| Yes | |
|
|
| Yes | |
DP master |
|
|
| |
| 125 | 125 |
| |
3. Interface |
|
|
| |
Interface type |
| Pluggable interface module (IF), technical data as for 2nd interface | Pluggable interface module (IF) | |
Plug-in interface modules |
| IF 964-DP (MLFB: 6ES7964-2AA04-0AB0) | IF 964-DP (MLFB: 6ES7964-2AA04-0AB0) | |
Physics |
| RS 485 / PROFIBUS | RS 485 / PROFIBUS | |
Functionality |
|
|
| |
|
| No | No | |
|
| Yes | Yes | |
|
| Yes | Yes | |
DP master |
|
|
| |
|
| 125 | 125 | |
Isochronous mode |
|
|
| |
Isochronous operation (application synchronized up to terminal) | Yes; For PROFIBUS only | Yes; For PROFIBUS only | Yes; Via PROFIBUS DP or PROFINET interface | |
Communication functions |
|
|
| |
PG/OP communication | Yes | Yes | Yes | |
Data record routing | Yes | Yes | Yes | |
Global data communication |
|
|
| |
| Yes | Yes | Yes | |
S7 basic communication |
|
|
| |
| Yes | Yes | Yes | |
S7 communication |
|
|
| |
| Yes | Yes | Yes | |
S5 compatible communication |
|
|
| |
| Yes; Via FC AG_SEND and AG_RECV, max. via 10 CP 443-1 or 443-5 | Yes; Via FC AG_SEND and AG_RECV, max. via 10 CP 443-1 or 443-5 | Yes; Via FC AG_SEND and AG_RECV, max. via 10 CP 443-1 or 443-5 | |
Standard communication (FMS) |
|
|
| |
| Yes; Via CP and loadable FB | Yes; Via CP and loadable FB | Yes; Via CP and loadable FB | |
Open IE communication |
|
|
| |
|
|
| Yes; via integrated PROFINET interface and loadable FBs | |
|
|
| 94 | |
| Via CP 443-1 and loadable FB | Via CP 443-1 and loadable FB | Yes; Via integrated PROFINET interface or CP 443-1 and loadable FBs | |
|
|
| 94 | |
|
|
| Yes; via integrated PROFINET interface and loadable FBs | |
|
|
| 94 | |
Web server |
|
|
| |
| No | No | Yes | |
Number of connections |
|
|
| |
| 96 | 96 | 96 | |
Standards, approvals, certificates |
|
|
| |
Use in hazardous areas |
|
|
| |
| ATEX II 3 G Ex nA IIC T4 Gc | ATEX II 3 G Ex nA IIC T4 Gc | ATEX II 3 G Ex nA IIC T4 Gc | |
Ambient conditions |
|
|
| |
Ambient temperature during operation |
|
|
| |
| 0 °C | 0 °C | 0 °C | |
| 60 °C | 60 °C | 60 °C | |
Configuration |
|
|
| |
Know-how protection |
|
|
| |
| Yes | Yes | Yes | |
| Yes; With S7 block Privacy | Yes; With S7 block Privacy | Yes; With S7 block Privacy | |
Dimensions |
|
|
| |
Width | 25 mm | 50 mm | 50 mm | |
Height | 290 mm | 290 mm | 290 mm | |
Depth | 219 mm | 219 mm | 219 mm | |
Weights |
|
|
| |
Weight, approx. | 700 g | 900 g | 900 g |