IEC60044-1, 2, 5, 6, GB1207, GB1208,GB16847, GBT4703, C57.13 | |
[艾爾電氣CT/PT互感器分析儀 產(chǎn)品簡(jiǎn)介] |
勵(lì)磁參數(shù)、匝比、匝比誤差、極性線圈電阻等多種參數(shù)分析測(cè)試。主要用于CT銘牌的參數(shù)校驗(yàn)、
CT接入當(dāng)前負(fù)荷時(shí)參數(shù)校驗(yàn)、PT的銘牌參數(shù)校驗(yàn)、PT二次負(fù)荷校驗(yàn)、CT的暫態(tài)特性對(duì)繼電保護(hù)
裝置的影響分析等等。
[艾爾電氣CT/PT互感器分析儀 產(chǎn)品特征] |
1、用于電流互感器的試驗(yàn):勵(lì)磁特性試驗(yàn);匝數(shù)比檢測(cè);比差與角差校驗(yàn);極性校驗(yàn);二次繞組
電阻測(cè)量;二次負(fù)荷測(cè)量;5%和10%誤差曲線測(cè)量;CT暫態(tài)特性測(cè)試與分析;CT銘牌自動(dòng)推斷;
拐點(diǎn)電壓/電流、準(zhǔn)確限值系數(shù)、儀表保安系數(shù)、二次時(shí)間常數(shù)、剩磁系數(shù)、準(zhǔn)確級(jí)、飽和與不飽
及電感等CT參數(shù)的測(cè)量。
2、用于電壓互感器的試驗(yàn):PT勵(lì)磁特性試驗(yàn);PT匝數(shù)比檢測(cè);PT極性校驗(yàn);PT二次繞組電阻測(cè)量;
PT二次負(fù)荷測(cè)量。
[艾爾電氣CT/PT互感器分析儀 產(chǎn)品參數(shù)] |
1、電流測(cè)量范圍:0~10A (自動(dòng)量程0.1/0.4/2/10A),誤差<±0.1%+0.01%FS;
2、電壓測(cè)量范圍:0~200 V (自動(dòng)量程1/10/70/200V),誤差< ±0.1%+0.01%FS;
3、匝數(shù)比測(cè)量范圍:1~10000,
誤差:1~1000 <0.05%,1000~2000 <0.1%,2000~5000 <0.2%;
4、 相位測(cè)量精度:±2min,分辨率:0.01min
5、二次繞組電阻測(cè)量范圍:0~8KΩ,誤差< 0.1%+0.01%FS分辨率:0.1mΩ;
6、CT二次負(fù)荷測(cè)量:0~160ohm,.1%+0.01%FS分辨率0.001ohm;
7、PT二次負(fù)荷測(cè)量:0~80kohm,.2%+0.02%FS分辨率0.1ohm;
8、溫度測(cè)量:-50~100度,誤差<3度;
9、輸入電源電壓:AC220V±10%,50Hz/60Hz±10%;
10、輸出電壓:0.1~125V(AC),輸出電流:0.001~5A(RMS),輸出功率:300VA;
11、數(shù)據(jù)存儲(chǔ)組數(shù):大于1000組;
12、工作條件: 溫度:-10℃~50℃, 濕度:≤90%;
13、尺寸:485mm×356mm×183mm;
14、重量:<13.6KG。
| |
根據(jù)用戶具體要求,設(shè)計(jì)相應(yīng)的產(chǎn)品配置方案。 | |
AL324 CT/PTMutual inductorAnalyzer
Implementation:
IEC60044-1, 2, 5, 6, GB1207, GB1208,GB16847, GBT4703, C57.13
Product brief:
CT/PT Analyzer, also known as the multi-purpose tester for current transformer characteristics, current transformer excitation characteristics and parameters of excitation, ratio, polarity, turn error-turn coil resistance analysis of multiple parameters, such as test. Main parameters for CT nameplate parameter calibration, calibration, CT access current load nameplate parameter calibration of PT, PT secondary load check, transient characteristics of CT analysis of relay protection devices and so on.
Product features:
1、for current transformer tests: excitation characteristic; Turns ratio testing; Difference with the calibration of angle difference; Polarity check; Secondary winding resistance measurement; Secondary load measurement; Curves and 5% error measurement; Transient characteristic test and analysis of CT; CT nameplate automatically inferred; Turning-point voltage/current, accuracy limit factor, instrument security factor, the secondary time constant, remanence factor, accuracy, and saturated with enough inductance measurement of CT parameters.
2, test for voltage transformer: excitation characteristic of PT, PT turns ratio test, calibration, PT PT polar secondary winding resistance measurement, measurement of PT secondary load.
Product parameter:
1、Current measurement range:0~10A (0.1/0.4/2/10A),Error<±0.1%+0.01%FS;
2、Voltage measurement range:0~200 V (1/10/70/200V),Error< ±0.1%+0.01%FS;
3、Turns ratio measurement range:1~10000,
Error:1~1000 <0.05%,1000~2000 <0.1%,2000~5000 <0.2%;
4、Phase measurement accuracy:±2min,Resolution:0.01min
5、Secondary winding resistance measurement range:0~8KΩ,Error< 0.1%+0.01%FSMaxResolution:0.1mΩ;
6、Measurement of CT secondary load:0~160ohm,Error0.1%+0.01%FSMaxResolution0.001ohm;
7、PT secondary load measurement:0~80kohm,Error0.2%+0.02%FSMaxResolution0.1ohm;
8、Temperature measurement:-50~100℃,Error<3℃;
9、Input power voltage:AC220V±10%,50Hz/60Hz±10%;
10、Output voltage:0.1~125V(AC),Current:0.001~5A(RMS),Power:300VA;
11、Data storage:1000Group number;
12、Working conditions:Temperature:-10℃~50℃,Humidity:≤90%;
13、Dimensions:485mm×356mm×183mm;
14、Weight:<13.6KG。