MultiFlame DM TV6-T Multi-spectrum多光譜火焰探測(cè)器,MultiFlame DM-TV6-T 是使用三個(gè)波長(zhǎng)多光譜紅外火焰探測(cè)器。DM-TV6-T 烴類火災(zāi)響應(yīng),并是為在骯臟的環(huán)境中運(yùn)行或煙熏火的檢測(cè)的正確選擇
特性:
- Flexible installation
- Configurable to suit application
- Immunity to false alarms
- Wide angle of vision
- Easy replacement of modules
- Wireless maintenance terminal
- Available in aluminium only
- Hart (R) option
- SIL 3
- 總覽:
-
The MultiFlame DM-TV6-T is a multi-spectrum infrared flame detector using three wavelengths. DM-TV6-T responds to hydrocarbon fires and is the right choice for operating in dirty environments or for the detection of smokey fires.
The DM-TV6-T is designed to respond to unwanted hydrocarbon fires, whilst maintaining a high degree of false alarm
immunity. The device offers a wide range of output options, as standard and is suitable for use in SIL 3 applications. The unit may be interfaced directly with a wide range of fire panels, controllers and PLC's etc.
The unit is fully configurable using a wireless handheLd terminaL (TLU) giving true flexibility to the installer. Time delays, sensitivity and output configuration are all set up via the TLU, a hazardous area approved handheld unit.
Wireless testing of the optical and output circuits is also possible using the TLU too
技術(shù)參數(shù):
GENERAL Type Flame detector Product Simtronics MultiFlame 3xIR Product code Standard range: DM-TV6-XTA0-*; Long range: DM-TV6-XTB0-* Manufacturer Simtronics FLAME DETECTOR Type / Principle Optical flame detection Technology Multispectrum Infrared flame detector Fire Types Hydrocarbon fires Modularity Replaceable sensor cartridge PERFORMANCE Cone of vision 110 deg horizontal, 95 deg vertical Response time 2 sec. Additional adjustable delay 3 - 20 sec Detection range: - n-heptane (1 sq ft fire) Standard: 40m (130ft). Long range: 80m (260ft) - Gasoline (1 sq ft fire) Standard: 33 m (110 ft). Long range: 65 m (210 ft) ELECTRICAL Power supply 24V DC, range (18 - 32V DC) Power consumption 70 mA normal; 155 mA during self test Cable entry 2x M20, one entry with Exd plug Junction box “No-touch” field cabling”, detector replaceable without opening cable glands Connection 0.3 mm2 (22 AWG) - 1.5 mm2 (16 AWG), 3 or 4 wires Analogue output signal 0-20mA, source, max. load impedance 700?. Fault signalling Diagnosis signalling in the 2.0 - 3.4mA range Relays 2 configurable relays for fire and fault Maintenance interface Wireless (IR) handheld terminal for configuration, test and diagnosis ENVIRONMENT Storage -40°C to +70°C (-40°F to 158°F) Operation -20°C to +60°C (-4°F to 140°F) Humidity 95% RH (non-condensing) Ingress IP66 RFI/EMI Complies with EN50081-1, EN50081-2, EN50082-1 and EN50082-2. HOUSING EX Classification Ex d II C T6 Material Epoxy coated aluminium or Stainless steel (Specify variant) Weight Aluminium: 3.3 Kg (7.3 lbs), Stainless steel: 7.4 kg (16.3 lbs) Dimensions 223L x 118D x 184H (mm), 8.78L x 4.65D x 7.25H (inches) APPROVALS ATEX Certificate DM LCIE 03 ATEX 6263 IECEx Certificate DM IECEx LCI09.0018 SIL Certificate Suitable for use in SIL3 systems ACCESSORIES TLU600 Infrared remote control unit LT15 Test lamp (EX flame simulation torch) AS008-350 Sunshade AS030-A/X Multi-position angle wall mounting AS035-A/X Pivot ball mounting bracket AS040 Sun visor (long, open) AS041 Sun visor (long, narrow)
文檔:
Product Sheet 377.89 KB
Operating Manual1.58 MB
Operating Manual (Italian)1.04 MB
Operating Manual (Portuguese)2.87 MB
證書:
ATEX Certificate2.06 MB
Certificate of Conformity CE363.96 KB
HART 7 Certification47.4 KB
IECEx Certification3.6 MB
SIL Certification DM-TV6-T541.91 KB
應(yīng)用:
• Refineries
• Drilling and Production PLatforms
• FueL Loading Facilities
• Compressor Stations
• LNG/LPG Processing and Storage
• Gas Turbines
• ChemicaL PLants
• Aircraft Hangars
• Sports Stadia / Atria