為了正確選擇自動控制閥的通徑,用戶需要了解下列事項: To properly size an automatic control valve you need to know the following: - Z和Z低的進口壓力
HighestLowest inlet pressures - 出口壓力
Outlet pressure - Z大流量要求
Maximum flow requirements - Z小流量要求
Minimum flow requirements
步驟1:利用流量表,并且在橫軸上找出符合用戶Z大流量要求的流量值。 Step 1: Utilize the high flow chartthe flow as found on the horizontal axis which corresponds with your maximum flow requirements. 步驟2:從這一點劃垂線,延伸到與相應(yīng)的Z小壓差的水平線相交。(此時,Z小壓差將是Z低進口壓力減去所需要的出口壓力,這也就是所說的∆P。) Step 2: From this point draw a vertical line until you intersect with the horizontal line corresponding with the minimum differential pressure. Your minimum differential pressure will be the lowest inlet pressure minus the desired outlet pressure, this is also known as the delta P. 步驟3:從這一點向右移動直到*個閥門的通徑線。這就是在25英尺/秒間歇流量時應(yīng)該采用的Z小閥門通徑。如果Z大流量是連續(xù)的,那么不要超過Z大連續(xù)流量表上所列的美制加侖/分鐘(20英尺/秒)。 Step 3: From this point move right to the first valve size line. This will be the minimum valve size which should be used on intermittent flow of 25 ft./sec. If maximum flow is continuous, then do not exceed the GPM 20 FT./sec. listed on the maximum continuous flow table. | | 步驟4:利用流量表,在豎軸上找到Z大壓差。(用戶的Z大壓差將是Z進口壓力減去所需要的出口壓力,這也就是所說的∆P。) Step 4: Utilize the flow chartthe maximum differential pressure as found on the vertical axis. Your maximum differential pressure will be the highest inlet pressure minus the desired outlet pressure, this is also known as the delta P. 步驟5:從這一點劃水平線與步驟3選擇的閥門通徑相應(yīng)的線相交。 Step 5: From this point draw a horizontal line until you intersect with the line corresponding to the valve size as selected in step 3. 步驟6:從這一點劃垂線向下與橫軸相交。這就是以這些變量為基礎(chǔ)的閥門的Z小流量能力。 Step 6: From this point draw a vertical line down to the horizontal axis. This will be the minimum flow capabilities of the valve based on these variables. 注意:1 如果通過步驟6得到的Z小流量能力比用戶實際的Z小流量要求,則用戶應(yīng)該考慮采用并聯(lián)安裝方式。采用這個Z小流量能力,從步驟1開始選擇用戶需要的用于低流量旁路的通徑。 2 采用空穴圖表并且確定進口和出口壓力的相交是否落在陰影區(qū)域內(nèi)。如果是,用戶應(yīng)該考慮串聯(lián)安裝方式。兩個閥門都應(yīng)該按照上述步驟選擇通徑。 Notes: 1 If the minimum flow capability obtained from step 6 is above your actual minimum flow requirements, you should consider a parallel installation. Using the minimum flow capability, begin at step 1 to the size you will need for this low-flow by-pass. 2 Use the cavitation chartdetermine if the intersection of the inletoutlet pressures falls in the shaded area. If so, you should consider a series installation. Both valves should be sized in accordance with the above steps. |