*HL55T(0.2級)電流互感器
上海源傾電氣有限公司主營產品:直流電阻測試儀,蓄電池組負載測試儀,回路電阻測試儀,微機繼電保護測試儀,接地電阻測試儀,高壓無線核相儀,*HL55T(0.2級)電流互感器,高壓試驗變壓器,直流單雙臂電橋,直流高壓發(fā)生器,管狀電加熱器,絕緣油介電強度測試儀,手表式近電報警器,氧化鋅 避雷器測試儀,絕緣電阻測試儀,高壓兆歐表,高壓絕緣墊,短路接地線等等
型號 | 主要技術指標 | |||
標準度 | 功率 | 額定 | 初級電流(A) | |
HL1 | 0.2 | 0.8 | 5 | 固定:15,50 穿心:100-150-200-300-600 |
HL1A | 0.1 | 0.8-1 | 10 | 固定:15,50 穿心:100-150-200-300-600 |
HL2 | 0.2 | 0.8 | 10 | 100-150-200-250-300-400-500-600-750-800-1000-1200-1500-2000 |
HL3 | 0.2 | 0.8 | 10 | 0.5-1-2-5-10-20-50 |
HL5-1 | 0.1 | 0.8或1 | 5 | 5-6-7.5-10-15-20-25-30-40-50-60-75-100-150-200-250-300-500-600-750-800-1000 |
HL16 | 0.1 | 0.8-1 | 10 | 300-400-500-600-750-1000-1500-2000-3000-4000 |
HL18 | 0.1 | 0.8-1 | 5 | 5-6-7.5-10-15-20-25-30-40-50-60-75-100-150-200-250-300-400-500 |
HL19 | 0.1 | 0.8-1 | 5 | 500-600-750-800-1000-2000-3000-4000-5000 |
HL23 | 0.1 | 0.8或1 | 5 | 0.5-1-2.5-5-10-25-50-100-150-200-250-300-400-500-600-700-750-1000-1200-1400-1500-1800-2000 |
HL23-1 | 0.2 | 0.8 | 10 | 0.5-1-2.5-5-10-25-50-100-150-200-250-300-400-500-600-700-750-1000-1200-1400-1500-1800-2000 |
HL23-2 | 5-10-25-50-100-150-200-250-300-400-500-600-700-750-1000-1200-1400-1500-1800-2000 | |||
HL23-3 | 15-30-50-75-150-200-300-400-600-700-800-1200-1400-1600 | |||
HL23-4 | 10-25-50-100-150-200-250-300-400-500-600-700-750-1000-1200-1400 | |||
HL23-5 | 0.25-0.5-1-2.5-5-10-25-50-100-150-200-250-300-400-500-600-700-750-900-1000-1200-1400-1500-1800-2000 | |||
HL23-9 | 0.1 | 0.8 | 10 | 0.1-0.25-0.5-1-2.5-5-10-25-50-100 |
HL24-1 | 0.2 | 0.8 | 10 | 10-25-50-100-150-200-300-600 |
HL24-2 | 10-25-50-100-200-250-500-1000 | |||
HL24-1A | 0.1 | 10-25-50-100-150-200-300-600 | ||
HL24-2A | 10-25-50-100-200-250-500-1000 | |||
0.5-1-2-2.5-5-10-15-20-25-30-50-75-100 | ||||
HL32-1 | 0.1 | 0.8-1 | 5 | |
HL32-2 | 10 | 0.5-2-2.5-5-10-15-20-25-30-50-75-100 | ||
HL34 | 0.02 | 1 | 5 | 5-7.5-10-15-20-25-30-40-50-60-75-100-150-200-250-300 |
HL35 | 0.1 | 1 | 5 | 0.5-0.75-1-1.5-2-2.5-3-4-5-7.5-10-15-20-25-30-40-50-60-75-100-150-200-250-300 |
HL35-1 | 0.1 | 0.8-1 | 10 | 0.5-0.75-1-1.5-2-2.5-3-4-5-7.5-10-15-20-25-30-40-50-75-100 |
HL35-2 | 5-7.5-10-15-20-25-30-40-50-60-75-80-100-120-150-200-250-300-400-500-600-750-800-1000-1500-2500-3000-4000-5000 | |||
HL35-4 | 15-20-25-30-40-50-60-80-100-150-200-250-300-400-500-600 | |||
HL36 | 0.2 | 0.8 | 10 | 100-150-200-250-300-400-500-600-750-800-1000-1200-1500-2000 |
HL36A | 0.1 | 0.8 | 10 | 100-150-200-250-300-400-500-600-750-800-1000-1200-1500-2000 |
HL36-1 | 0.2 | 0.8 | 5 | 100-150-200-250-300-400-500-600-750-800-1000-1200-1500-2000(二次為1A) |
HL36-1A | 0.1 | 0.8 | 5 | 100-150-200-250-300-400-500-600-750-800-1000-1200-1500-2000(二次為1A) |
HL37-4 | 0.2 | 0.8-1 | 10 | 15-20-25-30-40-50-60-80-100-150-200-250-300-400-500-600 |
HL41 | 0.1 | 0.8-1 | 5 | 0.1-0.15-0.2-0.25-0.3-0.4-0.5-0.6-0.75-1-1.5-2-2.5-3-4-5-6-7.5-10-15-20-25-30-40-50-60-75-80-100 |
HL42 | 0.2 | 0.8-1 | 5 | 0.1-0.15-0.2-0.25-0.3-0.4-0.5-0.6-0.75-1-1.5-2-2.5-3-4-5-7.5-10-15-20-25-30-40-50-75-80-100 |
HL50A | 0.05 | 1 | 10 | 5-7.5-10-15-20-25-30-40-50-60-75-80-100-120-150-200-250-300-400-500-600-750-800-1000-1200-1500-2000-2500-3000-4000-5000-6000-7500-8000-10000 |
HL55 | 0.2 | 0.8-1 | 5 | 端子:10-20-50 穿芯:100-150-200-300-600 |
HL55A | 0.1 | 0.8-1 | 5 | 端子:10-20-50 穿芯:100-150-200-300-600 |
HL55-1 | 0.2 | 0.8-1 | 5 | 端子:10-20-50 穿芯:100-150-200-300-600 (二次為1A) |
HL55-1A | 0.1 | 0.8-1 | 5 | 端子:10-20-50 穿芯:100-150-200-300-600 (二次為1A) |
HL55T | 0.2 | 0.2 | 5 | 端子:5-20-100 穿芯:200-300-600 |
主要技術要求:
2.1 額定容量:額定二次電流通過二次額定負荷時所消耗的視在功率。額定容量可以用視在功率V.A表示,也可以用二次額定負荷阻抗Ω表示。
2.2 一次額定電流:允許通過電流互感器一次繞組的用電負荷電流。用于電力系統(tǒng)的電流互感器一次額定電流為5~25000A,用于試驗設備的精密電流互感器為 0.1~50000A。電流互感器可在一次額定電流下*運行,負荷電流超過額定電流值時叫做過負荷,電流互感器*過負荷運行,會燒壞繞組或減少使用壽命。
2.3 二次額定電流:允許通過電流互感器二次繞組的一次感應電流。
2.4 額定電流比(變比):一次額定電流與二次額定電流之比。
2.5 額定電壓:一次繞組*對地能夠承受的大電壓(有效值以kV為單位),應不低于所接線路的額定相電壓。電流互感器的額定電壓分為0.5,3,6,10,35,110,220,330,500kV等幾種電壓等級。
2.6 10%倍數(shù):在的二次負荷和任意功率因數(shù)下,電流互感器的電流誤差為-10%時,一次電流對其額定值的倍數(shù)。10%倍數(shù)是與繼電保護有關的技術指標。
2.7 準確度等級:表示互感器本身誤差(比差和角差)的等級。電流互感器的準確度等級分為0.001~1多種級別,與原來相比準確度提高很大。用于發(fā)電廠、變電站、用電單位配電控制盤上的電氣儀表一般采用0.5級或0.2級;用于設備、線路的繼電保護一般不低于1級;用于電能計量時,視被測負荷容量或用電量多少依據(jù)規(guī)程要求來選擇(見*講)。
2.8 比差:互感器的誤差包括比差和角差兩部分。比值誤差簡稱比差,一般用符號f表示,它等于實際的二次電流與折算到二次側的一次電流的差值,與折算到二次側的一次電流的比值,以百分數(shù)表示。
2.9 角差:相角誤差簡稱角差,一般用符號δ表示,它是旋轉180°后的二次電流向量與一次電流向量之間的相位差。規(guī)定二次電流向量超前于一次電流向量δ為正值,反之為負值,用分(’)為計算單位。