意大利Elcontrol多功能電表、意大利Elcontrol多功能電表、意大利Elcontrol多功能電表、意大利Elcontrol多功能電表、
產(chǎn) 品 簡 介
供應(yīng)Elcontrol多功能電表 深圳市索晟科技有限公司代理意大利Elcontrol多功能電表、Elcontrol多功能電表、Elcontrol多功能電表、Elcontrol多功能電表、 Elcontrol STAR3 上等電能儀表。Elcontrol STAR3 上等電能儀表適用于高壓和低壓電力網(wǎng)路的多功能電表,可進行四象限電能測量,電流和電壓的諧波計算,電量參數(shù)監(jiān)測,并具有遙控和RS485的通訊功能。
主要熱賣型號有:STAR3、VIP 96、VIP96 PLUS、
STAR3 HARMO - ELCONTROL | COMMENTS | |
PICTURE | ||
MANUFACTURER | Elcontrol Energy Net -Italy | |
MEASURES | 52+102 harmo | |
DIMENSION | 96x96x115.4 | half depth |
MAX CABLE SIZE | 2.5 current and voltage. 1.5mm2 485 and options | bigger cables allowed |
CONNECTORS | all removable | easier to be removed and cabled |
IP INDEX | IP40 front , IP20 case | higher IP protection |
WEIGHT | 600gr | lower transport costs |
DISPLAY | backlit LCD with black baground and illuminated numbers | visible from longer distance |
VOLTAGE MEASUREMENTS | ||
MEASURED SYSTEMS | same | same |
DIRECT MEASUREMENTS | from 10 to 600 ph-ph from 6 to 350 ph-n | higher direct voltage |
VIA PT | primary 9999GV secondary: from 1 to 999 | wider range. Any secondary is allowed |
DISPLAY | from 0.000 to 9999GV | wider range |
OVERLOAD Permanent | 850 Vac | stands higher voltage |
update period | 1 sec | same |
CURRENT MEASUREMENTS | ||
VIA CT | primary 999GA secondary: from 1 to 999 | wider range. Any secondary is allowed |
MINIMUM CURRENT | 20 mA | not significant |
INPUT CONSUMPTION | total 1 VA at 5 Amp | not clear |
DISPLAY | From 0.000 to 9999GA | wider range |
OVERLOAD permanent | not declared | not comparable |
OVERLOAD intermittent | 50 amp for 1 sec | same |
UPDATE | 1 sec | same |
POWER | ||
Maximum ratio CTxPT | 9999GV*9999GA | wider range |
DISPLAY | 0 to 9999GW | wider range |
FREQUENCY | ||
RANGE | from 35 to 400 Hz | wider range |
ACCURACY | ||
Current | <0.25% from 10% to 110% In | similar |
Voltage | <0.25% from 10% to 110% In | similar |
Power | 0.5% of full scale | same |
POWER SUPPLY | ||
Voltage permitted | 90-230 AC from 0.1 to 400Hz | wider frequency range |
90-230 DC | wider range | |
not available | not available fro STAR3 | |
Consumption | <5VA | lower consumption, less heating |
OPERATING CONDITIONS | ||
Operating temp | -10°C to +50°C | similar |
Storage temp | -20°C to +85°C | same |
relative umidity | 90% | similar |
OPTIONAL FEATURES | ||
RS485 Modbus | included in all models | function always there |
Profibus | not avalable | not available in Star3 |
Pulse outputs | included in all models | function always there |
Alarms | included in all models | function always there |
4-20 mA | specific model | possibility to add later |
digital Inputs | possible on special contracts | not available in Star3 |
Harmonic analysis | included in all models | possibility to add later |
Memory for events | not available | not available in Star3 |
Connection test | not available | not available in Star3 |
OTHER FEATURES | ||
PROTECTION CODE | programmable value 6 digit. Acivated only if required | higher security and easier to use |