Hawke防爆連接器Hawke Power Ex connector
Hawke防爆連接器Hawke Power Ex connector
上海頤品自動化,:
Hawke Power Ex connector
Hazardous Area Connector
Tamb: -40°C to +60°C. II2 GD Exdb IIC Extb IIIC Db T85 IP66, 67 & DTS01 deluge protected.
Overview
The Power range of connectors have been designed specifically for the extremely demanding requirements of higher power applications.
Inserts are available with 1 to 4 contacts with a conductor acceptance range of between 50mm2 and 630mm2 operating up to 780A and 750V as standard. Other voltages available on special request.
Power
Connector Dimensions
For connector plugs and connector receptacles, cable glands are required to terminate incoming cables. These can be selected from the cable gland section of our website. These cable glands include but are not restricted to 501/453/Universal and the ICG 653/Universal.
DIMENSIONS (MM) | |||||
---|---|---|---|---|---|
Dimension | Ex32P | Ex40P | Ex50P | Ex63P | Ex75P |
A | 228 | 228 | 228 | 228 | 238 |
B | 168 | 168 | 168 | 168 | 178 |
ØC | 60 | 66 | 76 | 89 | 101 |
ØD | 73 | 79 | 89 | 102 | 114 |
E | 251 | 251 | 251 | 251 | 261 |
ØF | 67 | 73 | 82.5 | 95 | 108 |
ØP | 48 | 55 | 65 | 78 | 90 |
R | 60 | 60 | 60 | 60 | 60 |
S | 75.5 | 75.5 | 75.5 | 75.5 | 76 |
ØT | 61 | 68 | 77 | 90 | 102 |
U | 68.5 | 68.5 | 68.5 | 68.5 | 68.5 |
Thread V (1.5mm Pitch) | M32* | M40* | M50* | M63* | M75* |
ØW | 100 | 106 | 116 | 129 | 141 |
X | 184 | 184 | 184 | 184 | 194 |
* Other entry threads available upon request. |
Power
Inserts
INSERT SELECTION TABLE | ||||
---|---|---|---|---|
Configuration | ||||
Shell Size 32 | Shell Size 40 | Shell Size 50 | Shell Size 63 | Shell Size 75 |
1 x 50mm² + Earth | 1 x 185mm² + Earth | 3 x 50mm² + Earth | 3 x 95mm² + Earth | 3 x 185mm² + Earth |
1 x 70mm² + Earth | 1 x 240mm² + Earth | 3 x 70mm² + Earth | 3 x 120mm² + Earth | 3 x 240mm² + Earth |
1 x 95mm² + Earth | - | 4 x 50mm² + Earth | 3 x 150mm² + Earth | 4 x 185mm² + Earth |
1 x 120mm² + Earth | - | 4 x 70mm² + Earth | 4 x 95mm² + Earth | 4 x 240mm² + Earth |
1 x 150mm² + Earth | - | 1 x 185mm² + Earth | 4 x 120mm² + Earth | 1 x 500mm² + Earth |
- | - | 1 x 240mm² + Earth | 4 x 150mm² + Earth | 1 x 630mm² + Earth |
- | - | - | 1 x 300mm² + Earth | - |
- | - | - | 1 x 400mm² + Earth | - |
All Hawke Power![]() Other voltages and contact configurations also available contact us for details. |
Power
Calculations
To select the shell size of the connector, it is essential that you calculate the dissipated wattage of the arrangement. This ensures that the arrangement does not exceed the maximum permitted temperature classification with regard to the upper ambient temperature for the area of installation. (please refer to table 1 below for the maximum allowable dissipated wattage per connector size).
TABLE 1 | ||||||
---|---|---|---|---|---|---|
Connector Size | Upper Ambient Temperature of +40°C | Upper Ambient Temperature of +50°C | Upper Ambient Temperature of +60°C | |||
Temperature Class | Temperature Class | Temperature Class | ||||
T6 | T5 | T6 | T5 | T6 | T5 | |
Ex32P | 20.5W | 27.5W | 15.75W | 26W | 7.5W | 15.75W |
Ex40P | 22.5W | 30.5W | 17.5W | 28W | 8.7W | 17.5W |
Ex50P | 25.8W | 35.3W | 20W | 32.25W | 10W | 20W |
Ex63P | 30.2W | 41.5W | 23.5W | 37.7W | 11.7W | 23.5W |
Ex75P | 36.3W | 49.5W | 28.25W | 45.25W | 14W | 28.25W |
Maximum allowable dissipated wattage | ||||||
Other ambient temperature options can be extrapolated from table 1 above, or contact Hawke International for more information. |
TABLE 2 | ||
---|---|---|
Contact Size | Combined Cable And Contact Resistance (Ohms) | Contact Current Rating |
50mm² | 514 | 190 amps |
70mm² | 387 | 240 amps |
95mm² | 283 | 290 amps |
120mm² | 239 | 340 amps |
150mm² | 202 | 385 amps |
185mm² | 170 | 440 amps |
240mm² | 144 | 520 amps |
300mm² | 82 | 590 amps |
400mm² | 67 | 670 amps |
500mm² | 54 | 720 amps |
630mm² | 45 | 780 amps |
Dissipated Wattage Calculation
Equation definitions:
W = Dissipated wattage factor of the connector
N = The number of conductors to be terminated/number of contacts required. (Note: A contact comprises of a pin and socket).
I = The current requirement per contact. (Note: This must be equal to or less than the maximum current rating of the contact, as shown in table 2 above).
R = The combined cable and contact resistance (see table 2 above).
Values pertinent to these definitions must then be input into the relevant fields below to calculate the dissipated wattage (W) of your chosen arrangement:
1. W = N x I ² x R | |||
---|---|---|---|
N | I | R | Dissipated Wattage (Watts) W |
Note: The result must be lower than the maximum figure shown in table 1 above, for the appropriate temperature class and ambient temperature).
e.g. T6 40°C ambient application with 4 x 95mm² conductors running at 160 amps.
N = 4 contacts
I = 160 amps
R = 0.000283 ohms (95mm² soldered combined cable and contact resistance)
Therefore W = 4 x 25600 x 0.000283 = 28.9 watts.
Therefore an Ex63P Connector should be specified for this application as the shell size can accommodate the required 4 x 95mm² pin / socket inserts (see insert selection table) and the resultant dissipated wattage (28.9 watts) is below the maximum permitted 30.2 watts (see table 1 above).
This equation can also be transposed to facilitate the calculation of the maximum number of conductors permitted in your selected connector (calculator 2 below ) and the maximum allowable current within the upper ambient temperature of your location (calculator 3 below).
2. ![]() | |||
---|---|---|---|
W | R | I | Maximum Number Of Conductors N |
3. ![]() | |||
---|---|---|---|
W | N | R | Current (Amps) I |
Note: The result must not exceed the maximum current rating of the contacts (see table 2 above) |
Note: Unless otherwise requested, connectors will be marked as T5 with an upper ambient temperature of +40°C.
Order Codes
When ordering, select the relevant code from each block as shown in the example below:
Power/Exd-50-S-CR-A-4-50-S-FLFRC-A-1
Power![]() | Select Code | Description | Example Code | |
---|---|---|---|---|
Protection | Exd | Flameproof | Exd | |
Shell Size | 32 | 32 | 50 | |
40 | 40 | |||
50 | 50 | |||
63 | 63 | |||
75 | 75 | |||
Material | B | Brass Note: (for single core cables, Brass must be used) | S | |
S | Stainless Steel (as standard) | |||
N | Nickel Plated Brass | |||
Connector Style | CP | Connector Plug | CR | |
CR | Connector Receptacle | |||
BR | Bulkhead Receptacle | |||
Internal Earth Size Note: Should be at least 50% of phase conductor size | A | 50mm² | A | |
B | 70mm² | |||
C | 95mm² | |||
D | 120mm² | |||
E | 150mm² | |||
F | 185mm² | |||
G | 240mm² | |||
Number Of Contacts | See insert selection | |||
Contact Type | Contact Type | Maximum Conductor Acceptance Diameter (mm) | 50 | |
50 | 50mm² | 9.5 | ||
70 | 70mm² | 11.5 | ||
95 | 95mm² | 13 | ||
120 | 120mm² | 14.5 | ||
150 | 150mm² | 16.5 | ||
185 | 185mm² | 18.5 | ||
240 | 240mm² | 20.5 | ||
300 | 300mm² | 25 | ||
400 | 400mm² | 29 | ||
500 | 500mm² | 32 | ||
630 | 630mm² | 38 | ||
X | No Insert | |||
Insert Type | P | Pin | S | |
S | Socket | |||
Accessories * Note: only the connector receptacle (CR) can be flange mounted. | FL | Mounting Flange * | FLFRC | |
FPC | Flameproof Plug Cap | |||
FRC | Flameproof Receptacle Cap | |||
PPC | Environmental Plug Cap | |||
PRC | Environmental Receptacle Cap | |||
Certification | A | ATEX/IECEx/EAC/INMETRO | A | |
N | ATEX/IECEx/EAC/INMETRO /NEC 505 Voltage reduced to 600V | |||
Ambient Rating & Temperature Class T5 +40°C will be supplied as standard if alternative not specified | 1 | T5 +40°C Standard | 1 | |
2 | T5 +50°C | |||
3 | T5 +60°C | |||
4 | T6 +40°C | |||
5 | T6 +50°C | |||
6 | T6 +60°C |
Find A Connector Modifier
Ordering Information
For ordering information and codes, please see order codes tab.
中國區(qū)分銷商:
上海頤品自動化科技有限公司
Shanghai Epin Automation Co.,Ltd.
Website:www.epinautomation。。com
:sales@epinautomation.com
*: